Power Supply: AC220V, 50Hz Display: LCD
Output Voltage: AC 0V~80KV Or 0~100KV Accuracy: ±(1% Of Full Scale + 2 Digits)
Warranty: 1 Year Keyword: Insulation Oil Tester,Breakdown Voltage BDV Tester

IEC156 80kV Transformer Oil Breakdown Voltage BDV Tester

 

 

I.Introduction:

BDV-2 Transformer oil tester is developed according to DL/T846.7-2004 "Insulating oil dielectric tester" standard and the IEC/ASTM international standard. Built-in EEPROM memory can save 100 sets of test data, and test results can be printed at any time. It has the advantages of simple operation, powerful function, stable and reliable, and high degree of automation

 

II.Specifications:

No. Parameters Specifications
1 Output voltage AC 0V~80KV or 0~100KV
2 Rate of voltage rise 0.5kv/s± 5%, 2kv/s± 5%, 3kv/s± 5%, 5kv/s± 5%
3 Max. test times 9
4 Stir time 0~999s
5 Wait time 0~999s
6 Measurement accuracy ±(1% of full scale + 2 digits)
7 Resolution 0.1KV
8 Temperature measurement range 0°C to 70°C, or better
9 Temperature resolution 1°C, or better
10 Data storage 100 groups
11 Weight 38kg
12 Size 550 mm*500mm*580mm
13 Power supply AC220V, 50Hz
14 Working environment Room temperature to 45°C, humidity<85%